Siemens SINAMICS G120X Operating Instructions Manual page 570

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Note
When changing p0756, the parameters of the scaling characteristic (p0757, p0758, p0759, p0760) are overwritten with
the following default values:
For p0756 = 0, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 1, p0757 is set to 2.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 2, p0757 is set to 0.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 3, p0757 is set to 4.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 6, 7, p0757 is set to 0 °C, p0758 = 0.0 %, p0759 = 100 °C and p0760 = 100.0 %.
X202: IO module terminal
p0756[0...3]
CU analog inputs type / CU AI type
G120X_DP,
Access level: 2
G120X_USS
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the type of analog inputs.
p0756[0...1] = 0, 1, 4 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
p0756[0...2] = 2, 3 corresponds to a current input (r0752, p0757, p0759 are displayed in mA).
p0756[2...3] = 6, 7, 10 corresponds to a resistor input for temperature measurement (r0752, p0757, p0759 are
displayed in °C).
p0756[2...3] = 8 No temperature sensor connected. Mode for deactivating sensor monitoring (alarm A03520).
In addition, the associated DIP switch must be set.
For the voltage input, DIP switch AI0/1 must be set to "U".
For the current input, DIP switch AI0/1 or AI2 must be set to "I".
For the temperature input, DIP switch AI2 must be set to "TEMP".
Value:
0:
1:
2:
3:
4:
6:
7:
8:
10:
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Dependency:
See also: A03520
WARNING
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
If the system is operated when the load resistor is switched on (DIP switch set to "I"), the voltage between differential
inputs AI+ and AI- must not exceed 10 V or the injected 80 mA current otherwise the input will be damaged.
568
Unipolar voltage input (0 V ... +10 V)
Unipolar voltage input monitored (+2 V ... +10 V)
Unipolar current input (0 mA ... +20 mA)
Unipolar current input monitored (+4 mA to +20 mA)
Bipolar voltage input (-10 V ... +10 V)
Temperature sensor LG-Ni1000
Temperature sensor PT1000
No sensor connected
Temperature sensor DIN Ni 1k (6180 ppm / K)
Calculated: -
Scaling: -
Unit selection: -
Max:
10
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Integer16
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
[0] 4
[1] 4
[2] 8
[3] 8
SINAMICS G120X converter