Advanced commissioning
6.10 Energy saving
Parameters
Number
p29631[0...4]
p29632[0...4]
r29633
6.10.8

PROFIenergy

Overview
PROFIenergy is a standard based on PROFINET. PROFIenergy is certified and described in
the PROFIenergy profile of the PNO.
The higher-level controller transfers the control commands and status queries in acyclic
operation via data record 80A0 hex.
The converter supports the PROFIenergy profile V1.1 and the function unit class 3.
The converter supports PROFIenergy energy-saving mode 2.
Function description
Behavior of the converter with active energy-saving mode 2:
● The converter outputs alarm A08800.
● The RDY LED flashes green: 500 ms on, 3000 ms off.
● The converter does not send any diagnostic interrupts.
● If the higher-level controller goes to stop or the bus connection to the higher-level controller
is interrupted, the converter exits the energy-saving mode and resumes normal operation.
Example
You can find an application example for PROFIenergy on the Internet:
support.industry.siemens.com/cs/ww/en/view/41986454)
Parameters
Number
r5600
r5613
456
Name
Flow meter pump power
Flow meter pump flow
Flow meter calculated flow
For more information about the parameters, see Chapter "Parameter list (Page 470)".
PROFIenergy - saving energy with SIMATIC S7
Name
Pe energy-saving mode ID
CO/BO: Pe energy-saving active/inactive
(https://
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Factory setting
0.00 kW
0.00 m
/h
3
- m
/h
3
Factory setting
-
-