p29520
Multi-pump control enable / Mpc enab
Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Enables the multi-pump control function.
0: Multi-pump control inhibited
1: Multi-pump control enabled
Value:
0:
1:
Dependency:
The "Multi-pump control" function is only available for induction motors.
The "Multi-pump control" function is not supported on G120X converter variants of power rating 30kW or above.
Note
when P29520=0, P29521 can not set to a !0 value.
when P29520 value change from 1 to 0, P29521 value will change to 0 automatically
p29521
Multi-pump control motor configuration / Mpc mtr num config
Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Selects the number of motors that will be used as multi-pump control.
Value:
0:
1:
2:
3:
4:
5:
6:
Note
1X means motor power that configured in P307.
Currently multi-pump control only support that all motors should have the same power.
p29522
Multi-pump control motor selection mode / Mpc mtr sel mode
Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Parameter for selecting the control mode for swtiching-in and switching-out motors
Value:
0:
1:
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Disable MPC
Enable MPC
NONE
M1=1X
M1=1X,M2=1X
M1=1X,M2=1X,M3=1X
M1=1X,M2=1X,M3=1X,M4=1X
M1=1X,M2=1X,M3=1X,M4=1X,M5=1X
M1=1X,M2=1X,M3=1X,M4=1X,M5=1X,M6=1X
Fixed sequence
Absolute operating hours
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
6
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Parameters
7.2 Parameter list
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
915