Advanced commissioning
6.3 Drive control
p7610[0...79] contains the device names in ASCII format.

Changing device names - procedure

1. Change the device name either in the converter or via the controller:
– Converter: Change p7610
– Controller: Change the "object-name" property via the Write Property Service
2. Switch off the converter power supply to activate the name.
3. Wait until all LEDs on the converter are dark.
4. Switch on the converter power supply again.
Your settings become active after switching on.
The device name is now changed.

Restoring factory settings

The device name is retained when the factory settings are restored.
If you wish to reset the name to the factory setting, original value, proceed as described above
and set p7610[0] = 0.

Interconnecting analog outputs, restoring factory settings

If you set communication via BACnet, the converter switches its analog outputs with the
fieldbus.
The control then specifies the values which the converter outputs via its analog outputs.
To display a converter-specific value, you must change the interconnection of the analog
output.
Examples:
● AO 0 should display the value which the control specifies in the ANALOG OUTPUT 0 object.
In this particular case, no other settings are required in the converter.
● AO 1 should display the smoothed current actual value of the converter (r0027 smoothed
current actual value).
Interconnect p0771[1] with r0027: p0771[1] = 27
In this case, write access via the object ANALOG OUTPUT 1 results in an error message in
the control.

Reset to the factory setting for BACnet

When restoring the factory setting, the converter again uses the fieldbus to switch its analog
outputs.
278
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
SINAMICS G120X converter