Parameters
7.2 Parameter list
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency:
See also: p0205
Note
Wide voltage range device 500 V - 690 V:
The rated current displayed refers to a supply voltage of 500 V.
r0208
Rated power unit line supply voltage / PU U_rated
Access level: 2
Can be changed: -
Unit group: -
Min:
- [Vrms]
Description:
Displays the rated line supply voltage of the power unit.
r0208 = 400: 380 - 480 V +/-10 %
r0208 = 500: 500 - 600 V +/-10 %
r0208 = 690: 660 - 690 V +/-10 %
r0209[0...4]
Power unit maximum current / PU I_max
Access level: 3
Can be changed: -
Unit group: -
Min:
- [Arms]
Description:
Displays the maximum output current of the power unit.
Index:
[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
See also: p0205
p0210
Drive unit line supply voltage / U_connect
Access level: 3
Can be changed: T
Unit group: -
Min:
1 [V]
Description:
Sets the drive unit supply voltage (rms value of the phase-to-phase line supply voltage).
Dependency:
Set p1254, p1294 (automatic detection of the Vdc switch-on levels) = 0.
The switch-in thresholds of the Vdc_max controller (r1242, r1282) are then directly determined using p0210.
NOTICE
If, in the switched-off state (pulse inhibit), the supply voltage is higher than the entered value, the Vdc controller may
be automatically deactivated in some cases to prevent the motor from accelerating the next time the system is
switched on. In this case, an appropriate alarm A07401 is output.
504
Calculated: -
Scaling: -
Unit selection: -
Max:
- [Vrms]
Calculated: -
Scaling: -
Unit selection: -
Max:
- [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max:
63000 [V]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [Vrms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 8750, 8850,
8950
Factory setting:
- [Arms]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
400 [V]