6.8.6.1

Stall protection

Function description
If the load of a standard induction motor exceeds the stall torque of the motor, the motor can
also stall during operation on the converter. A stalled motor is stationary and does not develop
sufficient torque to accelerate the load.
If the "Motor model fault signal stall detection" r1746 for the time p2178 is present via the "Motor
model error threshold stall detection" p1745, the converter signals "Motor stalled" and fault
F07902.
Parameters
Number
r1408[0 ... 14]
p1745[D]
r1746
p2178[D]
r2198
6.8.6.2

No-load monitoring

Function description
An inadequate motor current indicates an interruption in the power transmission from the motor
to the load.
If the motor current for the time p2180 lies below the current level p2179, the converter signals
"output load not available" and alarm A07929.
Parameters
Number
r0068[0 ... 1]
p2179[D]
p2180[D]
r2197[0 ... 13]
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Name
CO/BO: Status word, current controller
Motor model error threshold stall detection
Motor model fault signal stall detection
Motor stalled delay time
CO/BO: Status word monitoring functions 2
Name
CO: Absolute actual current value
Output load detection current limit
Output load detection delay time
CO/BO: Status word monitoring functions 1
Advanced commissioning
6.8 Drive protection
Factory setting
-
5%
- %
0.01 s
-
Factory setting
- Arms
0 Arms
2000 ms
-
417