Warnings, faults and system messages
9.6 List of fault codes and alarm codes
Remedy:
- insert or remove the memory card.
- use a larger memory card.
- configure a longer trace time or use an endless trace.
- avoid saving parameters while a multiple trace is running.
- check whether other functions are presently accessing measurement result files.
A02097
MTrace 1: multiple trace cannot be activated
Reaction:
NONE
Acknowledge:
NONE
Cause:
The following functions or settings are not permissible in conjunction with a multiple trace (trace recorder 1):
- measuring function
- long-time trace
- trigger condition "immediate recording start" (IMMEDIATE)
- trigger condition "start with function generator" (FG_START)
Remedy:
- if required, deactivate the multiple trace (p4840[1] = 0).
- deactivate function or setting that is not permissible
See also: p4840 (MTrace cycle number setting)
A02098
MTrace 1: cannot be saved
Reaction:
NONE
Acknowledge:
NONE
Cause:
It is not possible to save the measurement results of a multiple trace on the memory card (trace recorder 1).
A multiple trace is not started or is canceled.
Alarm value (r2124, interpret decimal):
1: Memory card cannot be accessed.
- card is not inserted or is blocked by a mounted USB drive.
3: data save operation to slow.
- a second trace has been completed before the measurement results of the first trace were able to be saved.
- writing the measurement result files to the card is blocked by the parameter save.
4: Data save operation canceled.
- for instance, the file required for the data save operation was not able to be found.
See also: p4840 (MTrace cycle number setting)
Remedy:
- insert or remove the memory card.
- use a larger memory card.
- configure a longer trace time or use an endless trace.
- avoid saving parameters while a multiple trace is running.
- check whether other functions are presently accessing measurement result files.
A02099
Trace: Insufficient Control Unit memory
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory space still available on the Control Unit is no longer sufficient for the trace function.
Remedy:
Reduce the memory required, e.g. as follows:
- reduce the trace time.
- increase the trace clock cycle.
- reduce the number of signals to be traced.
See also: r4708, r4799
A02150
OA: Application cannot be loaded
Reaction:
NONE
992
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
SINAMICS G120X converter