Parameters
7.2 Parameter list
NOTICE
p1900 = 3:
This setting should only be selected if the motor data identification was already carried out at standstill.
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971).
During the rotating measurement it is not possible to save the parameter (p0971).
Note
The motor and control parameters of the vector control are only optimally set when both measurements are carried out
(initially at standstill, and then with the motor rotating). The measurement with rotating motor is not performed for p1300
< 20 (U/f controls).
An appropriate alarm is output when the parameter is set.
The switch-on command must remain set during a measurement and after the measurement has been completed, the
drive automatically resets it.
The duration of the measurements can lie between 0.3 s and several minutes. This time is, for example, influenced by
the motor size and the mechanical conditions.
p1900 is automatically set to 0 after the motor data identification routine has been completed.
If a reluctance motor has been parameterized, a pole position identification is carried out during the stationary
measurement. As a consequence, faults that occur can also be assigned to the pole position identification.
For U/f control (p1300), identification with speed controller optimization does not make sense (e.g. P1900 = 1).
p1900
Motor data identification and rotating measurement / MotID and rot meas
G120X_DP (PM330),
Access level: 2
G120X_PN (PM330),
Can be changed: C2(1), T
G120X_USS (PM330)
Unit group: -
Min:
0
Description:
Sets the motor data identification and speed controller optimization.
The motor identification should first be performed with the motor stationary (p1900 = 1, 2; also refer to p1910). Based
on this, additional motor and control parameters can be determined using the motor data identification with the motor
rotating (p1900 = 1, 3; also refer to p1960).
p1900 = 0:
Function inhibited.
p1900 = 1:
Sets p1910 = 1 and p1960 = 0, 1 depending on p1300
When the drive enable signals are present, a motor data identification routine is carried out at standstill with the next
switch-on command. Current flows through the motor which means that it can align itself by up to a quarter of a
revolution.
With the following switch-on command, a rotating motor data identification routine is carried out - and in addition, a
speed controller optimization by making measurements at different motor speeds.
p1900 = 2:
Sets p1910 = 1 and p1960 = 0
When the drive enable signals are present, a motor data identification routine is carried out at standstill with the next
switch-on command. Current flows through the motor which means that it can align itself by up to a quarter of a
revolution.
p1900 = 3:
Sets p1960 = 0, 1 depending on p1300
This setting should only be selected if the motor data identification was already carried out at standstill.
When the drive enable signals are present, with the next switch-on command, a rotating motor data identification
routine is carried out - and in addition, speed controller optimization by taking measurements at different motor speeds.
p1900 = 11, 12:
The same as p1900 = 1, 2 with the difference, that after the measurement, the system immediately goes into operation.
For this purpose, p1909.18 is set = p1959.13 is set = 1 .
Value:
0:
1:
2:
718
Inhibited
Identifying motor data and optimizing the speed controller
Identifying motor data (at standstill)
Calculated: -
Scaling: -
Unit selection: -
Max:
12
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
2
SINAMICS G120X converter