A02070

Trace: Parameter cannot be changed

Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace parameter settings cannot be changed when the trace is active.
See also: p4700, p4710, p4711, p4712, p4713, p4714, p4715, p4716, p4720, p4721, p4722, p4730, p4731, p4732, p4733,
p4780, p4781, p4782, p4783, p4789, p4795
Remedy:
- stop the trace before parameterization.
- if required, start the trace.
A02075

Trace: Pretrigger time too long

Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected pretrigger time must be shorter than the trace time.
See also: p4721, p4722
Remedy:
Check the pretrigger time setting and change if necessary.
F02080
Trace: Parameterization deleted due to unit changeover
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The trace parameterization in the drive unit was deleted due to a unit changeover or a change in the reference parameters.
Remedy:
Restart trace.
A02095

MTrace 0: multiple trace cannot be activated

Reaction:
NONE
Acknowledge:
NONE
Cause:
The following functions or settings are not permissible in conjunction with a multiple trace (trace recorder 0):
- measuring function
- long-time trace
- trigger condition "immediate recording start" (IMMEDIATE)
- trigger condition "start with function generator" (FG_START)
Remedy:
- if required, deactivate the multiple trace (p4840[0] = 0).
- deactivate function or setting that is not permissible
See also: p4840 (MTrace cycle number setting)
A02096

MTrace 0: cannot be saved

Reaction:
NONE
Acknowledge:
NONE
Cause:
It is not possible to save the measurement results of a multiple trace on the memory card (trace recorder 0).
A multiple trace is not started or is canceled.
Alarm value (r2124, interpret decimal):
1: Memory card cannot be accessed.
- card is not inserted or is blocked by a mounted USB drive.
3: data save operation to slow.
- a second trace has been completed before the measurement results of the first trace were able to be saved.
- writing the measurement result files to the card is blocked by the parameter save.
4: Data save operation canceled.
- for instance, the file required for the data save operation was not able to be found.
See also: p4840 (MTrace cycle number setting)
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Warnings, faults and system messages
9.6 List of fault codes and alarm codes