Fieldbus Interface Bacnet Settings / Bacnet Setting; Fieldbus Interface Bacnet Cov Increment / Bacnet Cov Incr - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
p2025[0...4]

Fieldbus interface BACnet settings / BACnet setting

G120X_USS
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the parameter for communication via BACnet.
p2025[0]:
Device object instance number (0 ... 4194303).
p2025[1]:
Maximum number of info frames (1 ... 10).
p2025[2]:
Number of APDU retries (0 ... 39).
p2025[3]:
Maximum master address (1 ... 127).
Index:
[0] = Device object instance number
[1] = Maximum number of info frames
[2] = Number of APDU retries
[3] = Maximum master address
[4] = Reserved
Dependency:
See also: p2030
p2026[0...74]

Fieldbus interface BACnet COV increment / BACnet COV incr

G120X_USS
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets BACnet COV (change of value) increment values.
738
Calculated: -
Scaling: -
Unit selection: -
Max:
4194303
Calculated: -
Scaling: -
Unit selection: -
Max:
4194303
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned32
Dynamic index: -
Function diagram: 9310
Factory setting:
[0] 1
[1] 5
[2] 3
[3] 32
[4] 0
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9310
Factory setting:
1
SINAMICS G120X converter

Advertisement

Table of Contents
loading