Voltage Generation Alternating Base Voltage Amplitude - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Description:
Displays the commissioning steps that have been carried out.
Bit field:
Bit
00
02
03
08
11
12
14
15
18
Note
The individual bits are only set if the appropriate action has been initiated and successfully completed.
The identification final display is reset when changing the type plate parameters.
r3926[0...n]
Voltage generation alternating base voltage amplitude / U_gen altern base
Access level: 4
Can be changed: -
Unit group: -
Min:
- [V]
Description:
Displays the base voltage for the alternating voltage in the context of motor data identification.
0:
No alternating voltages. The function is deactivated.
<0:
Automatic determination of the base voltage and wobbulation / self-setting based on the converter and the connected
motor.
Otherwise:
Base voltage for alternating current generation in volts (wobbulation active).
r3927[0...n]
Motor data identification control word / MotID STW
Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Successfully completed component of the last motor data identification carried out.
Bit field:
Bit
00
02
03
05
06
07
11
12
14
15
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Signal name
Motor/control parameters calculated (p0340 = 1, p3900 > 0) Yes
Motor data identification carried out at standstill (p1910 = 1) Yes
Rotating measurement carried out (p1960 = 1, 2)
Identified motor data are automatically backed up
Automatic parameterization as Standard Drive Control
Automatic parameterization as Dynamic Drive Control
First motor commissioning
Equivalent circuit diagram parameters changed
Circle identification executed
Signal name
Stator inductance estimate no measurement
Rotor time constant estimate no measurement
Leakage inductance estimate no measurement
Determine Tr and Lsig evaluation in the time range
Activate vibration damping
Deactivate vibration detection
Deactivate pulse measurement Lq Ld
Deactivate rotor resistance Rr measurement
Deactivate valve interlocking time measurement
Determine only stator resistance, valve voltage fault, dead
time
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
- [V]
Calculated: CALC_MOD_ALL Data type: Unsigned32
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
7.2 Parameter list
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
- [V]
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
847