Motor Model Status / Motmod Status - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
06
07
08
Dependency:
See also: p0500
CAUTION
Do not use bit 6 = 1 if the motor can be slowly reversed by the load at the torque limit. Long delay times due to blocking
(p2177 > p1758) can cause the motor to stall. In this case you should deactivate the function or use closed-loop control
throughout the speed range (note the information re bit 2 = 1).
Note
Bits 0 ... 2 only have an influence for sensorless vector control, bit 2 is pre-assigned depending on p0500.
For bit 2 = 1:
The sensorless vector control is effective down to zero frequency. A change is not made into the open-loop speed
controlled mode.
This operating mode is possible for passive loads. These include applications where the load itself does not generate
any active torque and therefore only acts reactively to the drive torque of the induction motor.
If bit 2 = 1, then bit 3 is automatically set to 1. Manual de-selection is possible and may be sensible if the saturation
characteristic (p1960) was not measured for third-party motors. Generally, for standard SIEMENS motors, the already
pre-assigned (default value) saturation characteristic is adequate.
When the bit is set, the selection of bits 0 and 1 is ignored.
For bit 2 = 0:
Bit 3 is also automatically deactivated.
For bit 6 = 1:
The following applies for sensorless vector control of induction motors:
For a blocked motor (see p2175, p2177) the time condition in p1758 is bypassed and a change is not made into open-
loop controlled operation.
For bit 7 = 1:
The following applies for sensorless vector control of induction motors:
If the changeover limits are parameterized too low (p1755, p1756), then they are automatically increased to rugged
values by the absolute amount p1749 * p1755.
The effective time condition for changing over into open-controlled operation is obtained from the minimum value of
p1758 and 0.5 * r0384.
Is recommended that bit 7 is activated for applications that demand a high torque at low frequencies, and at the same
time require low speed gradients..
Adequate parameterization of the current setpoint must be ensured (p1610, p1611).
For bit 8 = 1: no influence on the functionality of bits 0, 1, 2
The following applies for sensorless vector control of induction motors:
Changeover into open-loop speed controlled operation is no longer dependent on the speed setpoint (except for
OFF3), but instead is essentially dependent on time condition p1758. As a consequence, a drive can be started or
reversed in closed-loop speed controlled operation with setpoints from an external control system, if these briefly lie in
the open-loop speed control range.
r1751

Motor model status / MotMod status

Access level: 4
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the status of the motor model.
Bit field:
Bit
00
01
02
03
704
Closed-loop/open-loop controlled (PMSM) for a blocked
motor
Use rugged changeover limits
Closed-loop controlled until wait time p1758 has expired
Signal name
Controlled operation
Set ramp-function generator
Stop RsLh adaptation
Feedback
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Active
Active
Yes
Active
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
No
-
No
-
No
-
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
Inactive
6721
Inactive
-
No
-
Inactive
-
SINAMICS G120X converter