Profidrive Fault Delay / Pd Fault Delay; Profibus Additional Monitoring Time / Pb Suppl T_Monit; Co: Profidrive Pzd Receive Word / Pzd Recv Word - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

p2044

PROFIdrive fault delay / PD fault delay

G120X_DP,
Access level: 3
G120X_PN
Can be changed: T, U
Unit group: -
Min:
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the failure
while the drive is still operational (e.g. emergency retraction).
Dependency:
See also: r2043
See also: F01910
p2047

PROFIBUS additional monitoring time / PB suppl t_monit

G120X_DP
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the additional monitoring time to monitor the process data received via PROFIBUS.
Enables short bus faults to be compensated.
If no process data is received within this time, then an appropriate message is output.
Dependency:
See also: F01910
Note
For controller STOP, the additional monitoring time is not effective.
r2050[0...11]

CO: PROFIdrive PZD receive word / PZD recv word

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
NOTICE
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types. A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
100 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
20000 [ms]
Calculated: -
Scaling: 4000H
Unit selection: -
Max:
-
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 2410
Factory setting:
0 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 2410
Factory setting:
0 [ms]
Data type: Integer16
Dynamic index: -
Function diagram: 2440, 2468,
9360
Factory setting:
-
745