Siemens SINAMICS G120X Operating Instructions Manual page 172

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Figure 5-12
Ramp-down time for the OFF3 command
Motor data identification: Select the method which the converter uses to measure the data of
the connected motor:
● OFF: Motor data is not measured.
● STIL ROT: Recommended setting: Measure the motor data at standstill and with the motor
rotating. The converter switches off the motor after the motor data identification has been
completed.
● STILL: Measure the motor data at standstill. The converter switches off the motor after the
motor data identification has been completed.
Select this setting if one of the following cases is applicable:
– You have selected control mode "SPD N EN", but the motor cannot rotate freely.
– You have selected U/f control as control mode, e.g. "VF LIN" or "VF QUAD".
● ROT: Measure the motor data while the motor is rotating. The converter switches off the
motor after the motor data identification has been completed.
● ST RT OP: setting same as STIL ROT.
After the motor data identification, the motor accelerates to the current setpoint.
● STILL OP: setting same as STILL.
After the motor data identification, the motor accelerates to the current setpoint.
Complete quick commissioning:
Switchover the display using an arrow key: nO → YES
Press the OK key.
You have completed quick commissioning.
170
Ramp-up and ramp-down time of the motor
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
SINAMICS G120X converter