Eco Mode; Eco Mode Activation; Eco Mode Deactivation - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

6.10.2

ECO mode

Overview
ECO mode works by slightly changing the output voltage either up or down in order to find the
minimum input power. It is suitable for applications with a low dynamic response and constant
speed setpoint, and allows energy savings of up to 40% in the ideal case.
Precondition
The ECO mode can only work under conditions when the load characteristic is low dynamic.
The ECO mode works only in U/f control mode.
In the ECO mode, active slip compensation is necessary. Set the slip compensation (p1335) to
100 %. In the event of minor fluctuations in the setpoint, you have to raise the ramp-function
generator tolerance using p1148.
Function description

ECO mode activation:

When the speed setpoint is reached and remains unchanged for 5 s, the converter
automatically reduces its output voltage to optimize the motor's operating point.

ECO mode deactivation:

ECO mode is deactivated when the setpoint changes or if the converter's DC-link voltage is too
high or too low.
Parameters
Number
p1300
r1348
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Name
Open-loop/closed-loop control operating mode
CO: U/f control Eco factor actual value
For more information about the parameters, see Chapter "Parameters (Page 467)".
Advanced commissioning
6.10 Energy saving
Factory setting
20: Speed control
(encoderless)
--
437