Parameters

7.2 Parameter list

7.2
Parameter list
All objects: G120X_DP, G120X_PN, G120X_USS
r0002

Drive operating display / Drv op_display

Access level: 2
Can be changed: -
Unit group: -
Min:
0
Description:
Operating display for the drive.
Value:
0:
10:
12:
13:
14:
16:
17:
18:
19:
21:
22:
31:
35:
41:
42:
43:
44:
45:
46:
70:
200:
Dependency:
See also: r0046
NOTICE
For several missing enable signals, the corresponding value with the highest number is displayed.
Note
OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
p0003

Access level / Acc_level

Access level: 1
Can be changed: C1, T, U
Unit group: -
Min:
3
Description:
Sets the access level to read and write parameters.
Value:
3:
470
Operation - everything enabled
Operation - set "enable setpoint" = "1" (p1142)
Operation - RFG frozen, set "RFG start" = "1" (p1141)
Operation - set "enable RFG" = "1" (p1140)
Operation - MotID, excitation running
Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
Operation - braking with OFF3 can only be interrupted with OFF2
Operation - brake on fault, remove fault, acknowledge
Operation - DC braking active (p1230, p1231)
Ready for operation - set "Enable operation" = "1" (p0852)
Ready for operation - de-magnetizing running (p0347)
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
Switching on inhibited - carry out first commissioning (p0010)
Switching on inhibited - set "ON/OFF1" = "0" (p0840)
Switching on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
Switching on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
Switching on inhibited - supply STO terminal w/ 24 V (hardware)
Switching on inhibited - remove fault, acknowledge fault
Switching on inhibited - exit commissioning mode (p0010)
Initialization
Wait for booting/partial booting
Expert
Calculated: -
Scaling: -
Unit selection: -
Max:
200
Calculated: -
Scaling: -
Unit selection: -
Max:
4
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
3
SINAMICS G120X converter