Advanced commissioning
6.9 Drive availability
The principle of operation of the other parameters is explained in the following diagram and in
the table below.
The converter automatically acknowledges faults under the following conditions:
1)
● p1210 = 1 or 26: Always.
● p1210 = 4 or 6: If the command to switch-on the motor is available at a digital input or via the
● p1210 = 14 or 16: Never.
The converter attempts to automatically switch the motor on under the following conditions:
2)
● p1210 = 1: Never.
● p1210 = 4, 6, 14, 16, or 26: If the command to switch-on the motor is available at a digital input or
If, after a flying restart and magnetization (r0056.4 = 1) no fault occurs within one second, then the
3)
start attempt was successful.
Figure 6-89
Further information is provided in the parameter list.

Advanced settings

If you with to suppress the automatic restart function for certain faults, then you must enter the
appropriate fault numbers in p1206[0 ... 9].
Example: p1206[0] = 07331 ⇒ No restart for fault F07331.
426
fieldbus (ON/OFF1 = 1).
via the fieldbus (ON/OFF1 = 1).
Time response of the automatic restart