Reduce The Flux Setpoint In The Partial Load Range Of The Motor - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Advanced commissioning
6.10 Energy saving
Efficiency optimization, method 1
Figure 6-95
The motor operates in partial load mode between no-load operation and the rated motor torque.
Depending on p1580, in the partial load range, the converter reduces the flux setpoint linearly
with the torque.
Figure 6-96
The reduced flux in the motor partial load range results in higher efficiency.
Parameters
The converter calculates the parameters for the thermal motor model based on the motor data
that has been set – and the motor data identification.
Table 6-108 Efficiency optimization, method 2
Number
p1401[D]
p1570[D]
p3315[D]
p3316[D]
Table 6-109 Efficiency optimization, method 1
Number
p1570[D]
p1580[D]
436

Reduce the flux setpoint in the partial load range of the motor

Qualitative result of efficiency optimization, method 1
Name
Flux control configuration
CO: Flux setpoint
Efficiency optimization 2 minimum flux limit value
Efficiency optimization 2 maximum flux limit value
Name
CO: Flux setpoint
Efficiency optimization
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Factory setting
0000 0000 0000
0110 bin
100%
50%
110 %
Factory setting
100%
80%
SINAMICS G120X converter