Drive Commissioning Parameter Filter / Drv Comm. Par_Filt; Macro Drive Unit / Macro Drv Unit - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

4:
Note
A higher set access level also includes the lower one.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
p0010

Drive commissioning parameter filter / Drv comm. par_filt

Access level: 1
Can be changed: C2(1), T
Unit group: -
Min:
0
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
1:
2:
3:
5:
15:
29:
30:
39:
49:
Dependency:
See also: r3996
NOTICE
When the parameter is reset to a value of 0, short-term communication interruptions may occur.
Note
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Once the Control Unit has been booted up for the first time, the motor parameters suitable for the power unit have been
defined, and the control parameters have been calculated accordingly, p0010 is automatically reset to 0 if application
class is SDC as default(p96=1), or set as 1 if DDC as default(p96=2), depending on the power unit that is connected.
p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 = 15).
p0010 = 29, 39, 49: Only for internal Siemens use!
p0015

Macro drive unit / Macro drv unit

G120X_DP,
Access level: 1
G120X_PN
Can be changed: C1, C2(1)
Unit group: -
Min:
0
Description:
Runs the corresponding macro files(41/42/43/44/45/47/48/49/57).
Dependency:
See also: p1000, r8570
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Service
Ready
Quick commissioning
Power unit commissioning
Motor commissioning
Technological application/units
Data sets
Only Siemens internal
Parameter reset
Only Siemens internal
Only Siemens internal
Calculated: -
Scaling: -
Unit selection: -
Max:
49
Calculated: -
Scaling: -
Unit selection: -
Max:
999999
Parameters
7.2 Parameter list
Data type: Integer16
Dynamic index: -
Function diagram: 2800, 2818
Factory setting:
1
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
57
471