Default setting
Procedure for changing p0015 with the BOP-2 operator panel:
→ SETUP → ... → MAc PAr → P15 = X AI I-r → ... → FINISH
Default setting (macro) 47: "PID controller with internal fixed setpoint"
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Setting Parameter
p0015 = 46
46
AI 0 p1070[1] =
755[0]
AI 1 p1070[0] =
755[1]
AO 0 p0771[0] = 21
AO 1 p0771[1] = 27
Characteristics
4.2 Control interfaces
Setting Parameter
DI 0
p29652[1] = 722.0
p29650[0] = 1
ON/OFF1
p0840[0] = 29659.0
OFF2
p0844[0] = 29659.1
DI 1
p29652[0] = 722.1
DI 4
p0810 = 722.4
DI 5
p2104[0...1] = 722.5
DO 0
p0730 = 52.3
DO 1
p0731 = 52.2
DO 2
p0732 = 52.1
DO 3
p0733 = 52.7
Wiring
117