Drive Control Via Uss; On/Off Commands Via Uss; Activating Communication Via Fieldbus - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

6.3.6

Drive control via USS

6.3.6.1

Activating communication via fieldbus

Function description
Procedure
Proceed as follows to activate communication via USS:
1. Start quick commissioning.
2. In the first steps of the quick commissioning, confirm all of the values that have already been
set.
3. Select one of the following default settings:
– 54: "USS control"
– 55: "USS control local/remote"
4. In the next steps of the quick commissioning, confirm all additional values that have already
been set.
5. Exit quick commissioning.
You have activated communication via USS.

ON/OFF commands via USS

Selecting the macros 54 and 55 has the following effect:
● Only the ON/OFF2 command is possible via the terminal strip.
● The higher-level controller cannot turn the motor on or off.
To turn the motor on and off via the higher-level controller, you need to manually interconnect
the ON/OFF1 and OFF2 commands with the PROFIdrive control word:
● Set p0840[0] = r2090.0
● Set p0844[0] = r2090.1
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Default setting of the interfaces (macros) (Page 107)
Advanced commissioning