7.2 Parameter list
r1926[0...2]

Identified effective valve lockout time / t_lock_valve id

Access level: 4
Can be changed: -
Unit group: -
Min:
- [µs]
Description:
Displays the identified effective valve lockout time.
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
r1927[0...2]

Identified rotor resistance / R_rotor ident

Access level: 4
Can be changed: -
Unit group: -
Min:
- [ohm]
Description:
Displays identified rotor resistance (on separately excited synchronous motors: damping resistance).
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
p1959[0...n]

Rotating measurement configuration / Rot meas config

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the configuration of the rotating measurement.
Bit field:
Bit
01
02
03
04
11
12
13
14
Dependency:
See also: F07988
Note
The following parameters are influenced for the individual optimization steps:
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1, 3: p1400.0, p1458, p1459, p1470, p1472, p1496
726
Signal name
Saturation characteristic identification
Moment of inertia identification
Re-calculates the speed controller parameters
Speed controller optimization (vibration test)
Do not change the controller parameters during the
measurement
Measurement shortened
After measurement direct transition into operation
Calculate speed actual value smoothing time
Calculated: -
Scaling: -
Unit selection: -
Max:
- [µs]
Calculated: -
Scaling: -
Unit selection: -
Max:
- [ohm]
Calculated: CALC_MOD_ALL Data type: Unsigned16
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [µs]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [ohm]
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0000 0000 0001 1110 bin
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-