Advanced commissioning
6.3 Drive control
6.3.5.2

Setting the address

Function description
Procedure
1. Using parameter p2021, set the address using an operator panel or SINAMICS G120 Smart
Access.
Permissible addresses: 0 ... 31.
2. Switch off the converter power supply.
3. Wait until all LEDs on the converter are dark.
4. Switch on the converter power supply again.
Your settings become active after switching on.
You have set the bus address.
Parameters
Parameter
p2021
6.3.5.3

Parameters for setting communication via Modbus RTU

General settings
Fieldbus protocol selection
Baud rate
Setting range: 4800 bit/s ... 187500 bit/s
Parity
In the factory, the Control Unit is set for controllers with even parity You can adapt the parity at
your controller using p2031:
● p2031 = 0: No parity, 1 stop bit or 2 stop bits
● p2031 = 1: Odd parity, 1 stop bit
● p2031 = 2: Even parity, 1 stop bit
244
Description
Fieldbus interface address
p2030 = 2 (Modbus RTU)
p2020 = 7, 19200 bit/s
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Factory setting
0
SINAMICS G120X converter