Enable Pid Autotuning - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Number
p2350
p2354
p2355
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Name

Enable PID autotuning

Automatic controller setting based on the "Ziegler Nichols"
method.
After completion of the autotuning, the converter sets
p2350 = 0.
0: No function
1: The process variable follows the setpoint after a sudden
setpoint change (step function) relatively quickly, however
with an overshoot.
2: Faster controller setting than for p2350 = 1 with larger
overshoot of the controlled variable.
3: Slower controller setting than for p2350 = 1. Overshoot of
the controlled variable is, to a large extent, avoided.
4: Controller setting after completion of the autotuning as for
p2350 = 1. Optimize only the P and I action of the PID con‐
troller.
PID autotuning monitoring time
PID autotuning offset
Advanced commissioning
6.6 Technology controller
Factory setting
0
240 s
5%
363