7.2 Parameter list
NOTICE
For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switching on inhibited is acknowledged.
Only the signal source that originally switched on can also switch off again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0844[0...n]
BI: No coast-down / coast-down (OFF2) signal source 1 / OFF2 S_s 1
G120X_DP,
Access level: 3
G120X_PN
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the first signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switching on inhibited)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- no OFF2 (enable is possible)
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0844[0...n]
BI: No coast-down / coast-down (OFF2) signal source 1 / OFF2 S_s 1
G120X_USS
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the first signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switching on inhibited)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- no OFF2 (enable is possible)
588
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501, 8720,
8820, 8920
Factory setting:
[0] 2090.1
[1] 1
[2] 2090.1
[3] 2090.1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501, 8720,
8820, 8920
Factory setting:
[0] 29659.1
[1] 1
[2] 29659.1
[3] 29659.1
SINAMICS G120X converter