Output Reactor; Special Restrictions For Converter Fsg - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Description
2.6 Optional components
400 V Converter
frame size
FSD
FSE
FSF
FSG
Parallel connection between two line harmonics filters with 132 kW each
*)
The converters FSA are not assigned to a line harmonics filter. If the rated power of the line
harmonics filter is not exceeded, you may operate several convertors FSA on a common line
harmonics filter.

Special restrictions for converter FSG

When connecting 400 V converter FSG with line harmonics filters, parameter p1300 must be
set to 20.
For converter FSG with line harmonics filter, operation is only permissible in the vector control
mode. It is not permissible for U/f mode to be used.
2.6.4

Output reactor

Note
Output reactors are available as optional components for converters FSD ... FSJ.
The output reactor reduces the voltage rate of rise and dampens transient voltage peak at the
converter output, and enable longer motor cables to be connected.
36
Rated power (kW)
18.5
22
30
37
45
55
75
90
110
132
160
200
250
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Line harmonics filter
UAC:FN344019113E2FAJRX
UAC:FN344022115E2FAJRX
UAC:FN344030115E2FAJRX
UAC:FN344037115E2FAJRX
UAC:FN344045115E2FAJRX
UAC:FN344055115E2FAJRX
UAC:FN344075116E2FAJRX
UAC:FN344090116E2FAJRX
UAC:FN3440110118E2FAJRX
UAC:FN3440132118E2FAJXX
UAC:FN3440160118E2FAJXX
UAC:FN3440200118E2FAJXX
2x UAC:FN3440132118E2FAJXX
SINAMICS G120X converter
*)