List Of Fault Codes And Alarm Codes; Overview Of Faults And Alarms; Fault Codes And Alarm Codes; Internal Software Error - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Warnings, faults and system messages

9.6 List of fault codes and alarm codes

9.6
List of fault codes and alarm codes
9.6.1

Overview of faults and alarms

Overview
A message comprises a letter followed by the relevant number.
The letters have the following meaning:
A . . . .
F . . . .
N . . . .
9.6.2

Fault codes and alarm codes

All objects: G120X_DP, G120X_PN, G120X_USS
F01000

Internal software error

Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- evaluate fault buffer (r0945).
- carry out a POWER ON (switch-off/switch-on) for all components.
- if required, check the data on the non-volatile memory (e.g. memory card).
- upgrade firmware to later version.
- contact Technical Support.
- replace the Control Unit.
F01001
FloatingPoint exception
Reaction:
OFF2
Acknowledge:
POWER ON
970
Alarm code . . . .
Fault code . . . .
No report or internal message
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC