PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
support.industry.siemens.com/cs/ww/en/view/78788716)
Communication with the control system even if the line voltage is switched off
You must supply the converter with 24 V DC at terminals 31 and 32 if you wish to maintain
communication with the control system when the line voltage is switched off.
In the case of brief interruptions of the 24 V power supply, the converter may signal a fault
without communications with the control system being interrupted.
4.2.13.3

Installing the GSD

Procedure
1. Save the GSD on your PC via one of the following methods.
– With Internet access:
– Without Internet access:
2. Unzip the GSD file on your computer.
3. Import the GSD in the engineering system of the controller.
You have now installed the GSD file in the engineering system of the controller.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Controlling the speed of a SINAMICS G110M / G120 (Startdrive) with S7-1500 (TO) via
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
Insert a memory card into the converter.
Set p0804 to 12.
The converter writes the GSD as zipped file (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
Wiring
4.2 Control interfaces
(https://