Advanced commissioning
6.10 Energy saving
Parameters
Number
p0347[M]
p1260
r1261.0...11
p1262[D]
p1263
p1264
p1265
p1266
p1267
p1269[0...1]
p1274[0...1]
More information is provided in the parameter list.
More information
Interaction with other functions:
● Essential service mode
The activated "Essential service mode" function influences the "Bypass" function.
● Converter control
For operation of the motor on the line supply, the converter no longer responds to the OFF1
command, but rather only to OFF2 and OFF3.
● Temperature monitoring for the motor
The converter evaluates the temperature sensor in the motor, also for line operation of the
motor.
● Disconnecting the converter from the line supply
If for line operation of the motor, you disconnect the converter from the line supply, the
converter opens the K2 contactor and the motor coasts down.
To operate the motor on the line supply also for deactivated converter, the higher-level
control must supply the signal for the K2 line contactor.
444
Name
Motor de-excitation time
Bypass configuration (factory setting: 0)
0: Bypass is deactivated
3: Bypass without synchronization
Bypass control/status word
.00
1 signal: Close converter - motor contactor
.01
1 signal: Close line - motor contactor
Bypass dead time
Debypass (revert to drive) delay time
Bypass delay time
Bypass speed threshold
BI: Bypass control command
Bypass changeover source configuration
BI: Bypass switch feedback signal
[0]
1 signal: Converter - motor contactor is closed
[1]
1 signal: Line - motor contactor is closed
Bypass switch monitoring time
Parameters (Page 467)
Essential service mode (Page 429)
Motor protection with temperature sensor (Page 409)
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Factory setting
0 s
0
-
1 s
1 s
1 s
1480 rpm
0
0000 bin
[0] 1261.0
[1] 1261.1
1000 ms