p8405

Activate/deactivate RTC alarm A01098 / RTC A01098 act

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets whether the real-time clock outputs an alarm if the time is not synchronized (e.g. if the power supply was switched
off for an extended period).
Value:
0:
1:
Dependency:
See also: A01098
Note
RTC: Real-time clock
p8409

RTC DTC activation / RTC DTC act

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the activation/deactivation of the parameters for timers DTC1, DTC2, DTC3.
For p8409 = 0, the following applies:
DTC1 parameters p8410, p8411, p8412 are inactive and can be set. Binector output r8413.0 = 0.
DTC2 parameters p8420, p8421, p8422 are inactive and can be set. Binector output r8423.0 = 0.
DTC3 parameters p8430, p8431, p8432 are inactive and can be set. Binector output r8433.0 = 0.
For p8409 = 1, the following applies:
DTC1 parameters p8410, p8411, p8412 are active and cannot be set. Binector outputs r8413 are active.
DTC2 parameters p8420, p8421, p8422 are active and cannot be set. Binector outputs r8423 are active.
DTC3 parameters p8430, p8431, p8432 are active and cannot be set. Binector outputs r8433 are active.
Value:
0:
1:
Dependency:
See also: p8410, p8411, p8412, r8413, p8420, p8421, p8422, r8423, p8430, p8431, p8432, r8433
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8410[0...6]

RTC DTC1 weekday of activation / RTC DTC1 day act

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the weekday on which timer 1 is activated (DTC1).
The switch-on/off time is set in p8411/p8412 and the result displayed via binector output r8413.
Value:
0:
1:
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Alarm A01098 deactivated
Alarm A01098 activated
DTC inactive and can be set
DTC active and cannot be set
Weekday deactivated
Weekday activated
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Parameters
7.2 Parameter list
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
1
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
1
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
869