Jog 1 Speed Setpoint / Jog 1 N_Set - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Dependency:
See also: p0840, p1058
NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
G120X_DP,
Access level: 3
G120X_PN
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for jog 2.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
See also: p0840, p1059
NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
G120X_USS
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for jog 2.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
See also: p0840, p1059
NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1058[0...n]

Jog 1 speed setpoint / Jog 1 n_set

Access level: 2
Can be changed: T
Unit group: 3_1
Min:
-210000.000 [rpm]
Description:
Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
See also: p1055, p1056
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: p0505
Max:
210000.000 [rpm]
Parameters
7.2 Parameter list
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501, 3030
Factory setting:
[0] 0
[1] 722.1
[2] 0
[3] 0
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501, 3030
Factory setting:
0
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3001, 3030
Factory setting:
150.000 [rpm]
621

Advertisement

Table of Contents