Bacnet Objects - ABB i-bus KNX AC/S 1.x.1 Series Product Manual

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.11.5

BACnet objects

Type
Input
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Object name
Cooling distribution circuit: Supply setpoint temperature External
specification
Cooling distribution circuit: Return temperature
Cooling distribution circuit: Supply temperature
Cooling distribution circuit: Supply setpoint temperature status
Cooling distribution circuit: Outside temperature
Cooling distribution circuit: Supply setpoint temperature override
status
Cooling distribution circuit: Supply setpoint temperature External
specification
Cooling distribution circuit: Control On/Off
Cooling distribution circuit: Control On/Off override disable/enable
Cooling distribution circuit: Room control values
Cooling distribution circuit: Pump A override disable/enable
Cooling distribution circuit: Pump A override value
Cooling distribution circuit: Pump A operating status (Off/On)
Cooling distribution circuit: Pump A relay status
Cooling distribution circuit: Pump A fault
Cooling distribution circuit: Pump A repair switch status
Cooling distribution circuit: Pump B override disable/enable
Cooling distribution circuit: Pump B override value
Cooling distribution circuit: Pump B operating status (Off/On)
Cooling distribution circuit: Pump B relay status
Cooling distribution circuit: Pump B fault
Cooling distribution circuit: Pump B repair switch status
Cooling distribution circuit: Valve control value
Cooling distribution circuit: Valve override disable/enable
Cooling distribution circuit: Valve override control value
Cooling distribution circuit: Status Valve purge
Object type
Unit
COV send
condition
Analog value
°C (62)
-
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Binary value
-
Analog value
°C (62)
1.0
Binary value
-
-
Binary value
-
-
Analog value
% (98)
1.0
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Analog value
% (98)
1.0
Binary value
-
Analog value
% (98)
1.0
Binary value
-
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 361
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac/s 1.2.1Ac/s 1.1.1

Table of Contents