ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 99

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Multiplexer, n-fold (n-MUX)
Selects a value from up to 16 input values.
Inputs
No.
1
2
3
4-17
Outputs
No.
1
2
Parameters
Name
Input count
Function
The selector value defines which input value is sent to the output.
Values received on unselected inputs are stored until the input is selected.
The output is recalculated and updated every time if any of the inputs or Select receives a value.
The selector starts with the value 0.
Exception
If the value on the selected input or on the selector is invalid, the output will not react.
The output F (Error) is set to 1. It resets to 0 as soon as both the selector and the selected input have valid
values.
Other
If an unlinked input is selected, the output value remains unchanged.
DPT
1 byte unsigned
2 bytes unsigned
4 bytes unsigned
Any
Any
Any
DPT
Abbr.
Any
W
1 bit
F
Value
2...16
Note
Abbr.
Name
S
Selector
I
Input value
0
I
Input value
1
I
Input value
n
Name
Value
Error
Visible
Description
Always
Always
Always
Parametrizable
n = 2...15
Visible
Description
Always
Always
Visible
Description
Always
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 99