ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 217

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object function
Input: Split unit, fan speed
The module has this group object if the Yes option is selected for the
Input for the fan speed in the split unit.
Telegram value:
Input: Split unit, status
The module has this group object if the Yes option is selected for the
Input for the status of the split unit.
Telegram value:
0...100%
0 = Auto
1 = Heat
2 = Morning Warmup
3 = Cool
4 = Night Purge
5 = Precool
6 = Off
7 = Test
8 = Emergency Heat
9 = Fan only
0A = Free Cool
0B = Ice
0C = Maximum Heat Mode
0D = Economic Heat/Cool Mode
0E = Dehumidification
0F = Calibration Mode
10 = Emergency Cool Mode
11 = Emergency Steam Mode
14 = No Dem
Name (can be changed
separately)
Room
Split unit
parameter.
Room
Split unit
parameter.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 217
Data type
Flags
1 byte
C, W, T, U
DPT 5.001
1 byte
C, W, T, U
DPT 20.105