ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 316

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Pump fault
The module has this output socket if the Yes option is selected for the
Outputs the fault status provided by the pump.
Signal value:
Pump repair switch status
The module has this output socket if the Yes option is selected for the
Outputs the contact position provided by the pump repair switch.
Signal value:
Pump override disable/enable
The module has this output socket if the Yes option is selected for the
Outputs whether the heat generator's pump is overridden.
Signal value:
Pump override value
The module has this output socket if the Yes option is selected for the
Outputs the state with which the heat generator's pump is overridden if the pump override is active.
Signal value:
Supply setpoint temperature
The module has this output socket if the Yes option is selected for the
Outputs the current supply setpoint temperature as is sent by the module to the heat generator via the related group object.
The supply setpoint temperature output here is, depending on the setting, either calculated by this module based on the
outside temperature, or specified via an ASM input socket or BACnet and also takes into account any possible override of the
supply setpoint temperature via the web user interface.
Signal value:
Supply setpoint temperature External specification
This module has this output socket if the Yes option is selected for the
input object option is selected for the
Outputs the supply setpoint temperature specified via the BACnet object. This status does not take into account any possible
override of the supply setpoint temperature via the web user interface.
Signal value:
316 2CDC508198D0211 Rev. A | AC/S 1.x.1
0 = No alarm
1 = Alarm
0 = Inactive
1 = Active
0 = Disabled
1 = Enabled
0 = Off
1 = On
-273...670760 °C
Supply setpoint temperature source
-273...670760 °C
Data type
DPT 1.005
Pump display pump fault status
DPT 1.011
Display pump repair switch status
DPT 1.003
Override by WebUI
parameter.
DPT 1.001
Override by WebUI
parameter.
DPT 9.001
Supply temperature control
parameter.
DPT 9.001
Supply temperature control
parameter and the BACnet
parameter.
parameter.
parameter.