ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 359

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object function
Input: Pump B fault
The module has this group object if the Yes option is selected for the
for the
The fault state of the second pump can be received via this group object and evaluated by the device
Telegram value:
In-/Output: Pump B override
disable/enable
The module has this group object if the Yes option is selected for the
for the
This object activates/deactivates the second pump override for the cooling distribution circuit controller.
Telegram value:
In-/Output: Pump B override value
The module has this group object if the Yes option is selected for the
for the
This object specifies the state with which the second pump for the cooling distribution circuit is overridden if the second pump
override is active.
Telegram value:
Input: Pump B repair switch status
The module has this group object if the Yes option is selected for the
for the
The status of the repair switch for the second pump can be received via this group object and evaluated by the device.
Telegram value:
Pump display pump fault status
0 = Inactive
1 = Active
Override by WebUI
parameter.
0 = Disabled
1 = Enabled
Override by WebUI
parameter.
0 = Off
1 = On
Display pump repair switch status
0 = Inactive
1 = Active
Name (can be changed separately)
Cooling distribution circuit
Double pump
parameter.
Cooling distribution circuit
Double pump
Cooling distribution circuit
Double pump
Cooling distribution circuit
Double pump
parameter.
Data type
Flags
1 bit
C, W, T
DPT 1.011
parameter and the Yes option is selected
1 bit
C, R, W, T
DPT 1.003
parameter and the Yes option is selected
1 bit
C, R, W, T
DPT 1.001
parameter and the Yes option is selected
1 bit
C, W, T
DPT 1.011
parameter and the Yes option is selected
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 359