ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 387

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Supply setpoint temperature
The module has this output socket if the Yes option is selected for the
Outputs the current supply setpoint temperature as is sent by the module to the chiller via the related group object. The supply
setpoint temperature output here is, depending on the setting, either calculated by this module based on the outside
temperature, or specified via an ASM input socket or BACnet and also takes into account any possible override of the supply
setpoint temperature via the web user interface.
Signal value:
Supply setpoint temperature External specification
This module has this output socket if the Yes option is selected for the
input object option is selected for the
Outputs the supply setpoint temperature specified via the BACnet object. This status does not take into account any possible
override of the supply setpoint temperature via the web user interface.
Signal value:
Chiller operating status
The module has this output socket if the Yes option is selected for the
Outputs the operating status (Off/On) provided by the chiller. Due to the control integrated into the chiller, this status may differ
from the operating status specified by this module.
Signal value:
Chiller fault status
The module has this output socket if the Yes option is selected for the
Outputs the fault status provided by the chiller.
Signal value:
-273...670760 °C
Supply setpoint temperature source
-273...670760 °C
0 = Off
1 = On
0 = Off
1 = On
Data type
DPT 9.001
Supply temperature control
parameter.
DPT 9.001
Supply temperature control
parameter and the BACnet
parameter.
DPT 1.001
Show operating status
parameter.
DPT 1.001
Show fault status
parameter.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 387