ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 395

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Chiller: Chiller operating status
The module has this BACnet output object if the Yes option is selected for the
Outputs the operating status (Off/On) provided by the chiller. Due to the control integrated into the chiller, this status may differ
from the operating status specified by this module.
Signal value:
Chiller: Chiller fault status
The module has this BACnet output object if the Yes option is selected for the
Outputs the fault status provided by the chiller.
Signal value:
Chiller: Room control values
The module has this BACnet output object if the Yes option is selected for the
Outputs the highest room setpoint temperature that is present on the ASM input socket and that is used by the Switch off if no
room demand function.
Signal value:
Chiller: Pump override disable/enable
The module has this BACnet output object if the Yes option is selected for the
Outputs whether the pump for the chiller is overridden.
Signal value:
0 = Off
1 = On
0 = Off
1 = On
0...100 %
0 = Disabled
1 = Enabled
Object type
Unit
Binary value
-
Show operating status
parameter.
Binary value
-
Show fault status
parameter.
Analog value
% (98)
Switch off if no room demand
parameter.
Binary value
-
Override by WebUI
parameter.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 395
COV send
condition
-
-
1.0
-