ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 202

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Split unit, On/Off
The module has this output socket if the Yes option is selected for the
Outputs the operating status of the split unit.
Signal value:
Split unit, fan speed
The module has this output socket if the Yes option is selected for the
Outputs the fan speed in the split unit.
Signal value:
Split unit, status
The module has this output socket if the Yes option is selected for the
Outputs the status of the split unit.
Signal value:
202 2CDC508198D0211 Rev. A | AC/S 1.x.1
0 = Off
1 = On
0...100 %
0 = Auto
1 = Heat
2 = Morning Warmup
3 = Cool
4 = Night Purge
5 = Precool
6 = Off
7 = Test
8 = Emergency Heat
9 = Fan only
0A = Free Cool
0B = Ice
0C = Maximum Heat Mode
0D = Economic Heat/Cool Mode
0E = Dehumidification
0F = Calibration Mode
10 = Emergency Cool Mode
11 = Emergency Steam Mode
14 = No Dem
Data type
DPT 1.001
Split unit
parameter.
DPT 5.001
Split unit
parameter.
DPT 20.105
Split unit
parameter.