ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 245

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Selection of ASM input socket or BACnet input object option:
Dependent parameter(s):
Supply setpoint temperature offset
Options:
0...100 °C
An offset can be entered to compensate for the energy losses in the pipes. This value is
always added to the supply setpoint temperature and is limited by the Max. supply
temperature parameter.
Selection of WebUI Input or BACnet input object option:
Dependent parameter(s):
Initial values
Supply setpoint temperature
Options:
0...80...100 °C
This parameter defines the supply setpoint temperature that is output after downloading the
module. This value is output until a new value is entered on the web user interface or is
written to the BACnet object. This value is limited by the Max. supply temperature
parameter.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 245