ABB i-bus
KNX
Parameters
BACnet output objects
Object name
Room: Actual room temperature
Outputs the actual room temperature.
Signal value:
Room: Room setpoint temperature
Outputs the current room setpoint temperature.
Signal value:
Room: Controller On/Off
The module has this BACnet output object if the Display or Display+set (slave) option is selected for the
parameter.
Outputs whether the room thermostat is switched on or off.
Signal value:
Room: Heating/cooling operating type
The module has this BACnet output object if any option except None is selected for the
parameter.
Outputs the current heating/cooling operating type.
Signal value:
Room: Operating mode
The module has this BACnet output object if any option except None is selected for the
Outputs the current HVAC operating mode.
Signal value:
-273...670760 °C
-273...670760 °C
0 = Off
1 = On
0 = Cooling
1 = Heating
0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
Object type
Unit
Analog value
°C (62)
Analog value
°C (62)
Binary value
-
Controller On/Off
Binary value
-
Heating/cooling operating type
Positive integer
No unit (95)
value
Operating mode
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 219
COV send
condition
1.0
1.0
-
-
1.0
parameter.