ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 216

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object function
Input: Floor temperature sensor
The module has this group object if the On/Off option or the 0...100 % option is selected for the
the Yes option is selected for the Floor temperature sensor parameter.
Input for the floor temperature.
Telegram value:
Input: Cooling ceiling, valve
Input for the position (control value) of the cooling ceiling valve.
The data point type for the group object is dependent on the settings in the module:
If the On/Off option is selected for the
DPT 1.001
Telegram value 0 = Off, 1 = On
If the 0...100 % option is selected for the
DPT 5.001
Telegram value 0...100 %
Input: Cooling ceiling, dew point alarm sensor
The module has this group object if the On/Off option or the 0...100 % option is selected for the
the Yes option is selected for the Cooling ceiling, dew point alarm sensor parameter.
Input for the signal value from the dew point sensor in the cooling ceiling.
Telegram value:
Input: Split unit, On/Off
The module has this group object if the Yes option is selected for the
Input for the operating status of the split unit.
Telegram value:
216 2CDC508198D0211 Rev. A | AC/S 1.x.1
-273...670760 °C
Cooling ceiling
Cooling ceiling
-273...670760 °C
0 = Off
1 = On
Name (can be changed
separately)
Room
Room
parameter:
parameter:
Room
Room
Split unit
parameter.
Data type
Flags
2 bytes
C, W, T, U
DPT 9.001
Floor heating
parameter and
1 bit DPT 1.001
C, W, T, U
1 byte DPT 5.001
2 bytes
C, W, T, U
DPT 9.001
Cooling ceiling
parameter and
1 bit
C, W, T, U
DPT 1.001