ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 151

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Send value to KNX by a change of
Options:
This parameter changes the send behavior. The value is only sent on the KNX bus if the new value differs
from the last value sent by the difference set. The value "0" means that this function is not active and any
value change on the web user interface is sent on the bus. This function affects only the output on the
KNX bus. The last value set on the web user interface is always output on the ASM output socket.
Send cyclically values to KNX
Options:
This parameter specifies whether the value is to be sent cyclically on the KNX bus.
No (checkbox cleared): The value is only sent on the KNX bus after a change.
Yes (checkbox selected): The value is sent on the KNX bus after every change and cyclically. The
cycle time is set in the Send cyclically values to KNX every parameter below and is restarted each
time on sending after a change.
Selection of Yes option:
Initial values
Initial value
This parameter defines the value that is output after downloading the module. This value is output on the
web user interface and the ASM socket until a new value in the group object overwrites it.
The value range is dependent on the data point type set.
0...1...670760 °C
(Value range dependent on the data point type selected)
No (checkbox cleared)
Yes (checkbox selected)
Dependent parameter(s)
Send cyclically values to KNX every
Options:
00:10:00...01:00:00...23:59:00 [hh:mm:ss]
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 151