ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 233

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Initial values
Here the initial room setpoint temperatures are set for the related operating modes that are active in the
application controller after downloading the ASM. The previous values are restored after a device restart.
There are only settings for the operating modes for which the checkbox is selected in the Interfaces
parameter.
The room setpoint temperatures can be set in the range from 0 °C - 50 °C. A validation process checks
whether the following sequence is maintained:
4.
5.
6.
7.
8.
9.
10. Heating Standby
11. Heating Economy
12. Heating Building Protection
Every room setpoint temperature must equal to or greater than the previous. Furthermore, the dead band
set must be respected. Otherwise the incorrect fields are marked with a red frame.
Cooling Building Protection
Options:
Cooling Economy
Options:
Cooling Standby
Options:
Cooling Comfort
Options:
Heating Comfort
Options:
Heating Standby
Options:
Heating Economy
Options:
Heating Building Protection
Options:
Cooling Building Protection
Cooling Economy
Cooling Standby
Cooling Comfort
Dead band
Heating Comfort
0...40...50 °C
0...27...50 °C
0...25...50 °C
0...20...50 °C
0...20...50 °C
0...19...50 °C
0...17...50 °C
0...3...50 °C
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 233