ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 321

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object function
Input: Pump operating status (Off/On)
The module has this group object if the Yes option is selected for the
Input for the operating status (Off/On) provided by the pump.
Telegram value:
Input: Pump fault
The module has this group object if the Yes option is selected for the
Input for the fault status provided by the pump.
Telegram value:
Input: Pump repair switch status
The module has this group object if the Yes option is selected for the
Input for the contact position provided by the pump repair switch.
Telegram value:
Name (can be changed separately)
Heat generator
0 = Inactive
1 = Active
Heat generator
0 = Inactive
1 = Active
Heat generator
0 = Inactive
1 = Active
Data type
1 bit
DPT 1.011
Pump display operating status
parameter.
1 bit
DPT 1.011
Pump display pump fault status
1 bit
DPT 1.011
Display pump repair switch status
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 321
Flags
C, W, T
C, W, T
parameter.
C, W, T
parameter.