ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 328

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Heat generator: Pump override disable/enable
The module has this BACnet output object if the Yes option is selected for the
Outputs whether the heat generator's pump is overridden.
Signal value:
Heat generator: Pump override value
The module has this BACnet output object if the Yes option is selected for the
This object specifies the state with which the heat generator's pump is overridden if the pump override is active.
Signal value:
Heat generator: Pump operating status (Off/On)
The module has this BACnet output object if the Yes option is selected for the
Outputs the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the heat generator.
Signal value:
Heat generator: Pump relay status
Outputs the status of the heat generator's pump.
Signal value:
328 2CDC508198D0211 Rev. A | AC/S 1.x.1
0 = Disabled
1 = Enabled
0 = Off
1 = On
0 = Inactive
1 = Active
0 = Off
1 = On
Object type
Unit
Binary value
-
Override by WebUI
parameter.
Binary value
-
Override by WebUI
parameter.
Binary value
-
Pump display operating status
parameter.
Binary value
-
COV send
condition
-
-
-
-