ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 283

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Heating distribution circuit: Pump B override disable/enable
The module has this BACnet output object if the Yes option is selected for the
selected for the
Outputs whether the heating distribution circuit's second pump is overridden.
Signal value:
Heating distribution circuit: Pump B override value
The module has this BACnet output object if the Yes option is selected for the
selected for the
This object specifies the state with which the heating distribution circuit's second pump is overridden if the pump override is
active.
Signal value:
Heating distribution circuit: Pump B operating status (Off/On)
The module has this BACnet output object if the Yes option is selected for the
selected for the
Outputs the operating status (Off/On) provided by the second pump. On pumps with their own control, this operating status
can differ from the operating status of the heating distribution circuit controller.
Signal value:
Heating distribution circuit: Pump B relay status
The module has this BACnet output object if the Yes option is selected for the
Outputs the status of the second pump from the heating distribution circuit controller.
Signal value:
Override by WebUI
parameter.
0 = Disabled
1 = Enabled
Override by WebUI
parameter.
0 = Off
1 = On
Pump display operating status
parameter.
0 = Inactive
1 = Active
0 = Off
1 = On
Object type
Unit
Binary value
-
Double pump
parameter and the Yes option is
Binary value
-
Double pump
parameter and the Yes option is
Binary value
-
Double pump
parameter and the Yes option is
Binary value
-
Double pump
parameter.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 283