ABB i-bus
KNX
Parameters
Object name
Cooling distribution circuit: Pump B override value
The module has this BACnet output object if the Yes option is selected for the
selected for the
This object specifies the state with which the second pump for the cooling distribution circuit is overridden if the pump override
is active.
Signal value:
Cooling distribution circuit: Pump B Operating Status (Off/On)
The module has this BACnet output object if the Yes option is selected for the
selected for the
Outputs the operating status (Off/On) provided by the second pump. On pumps with their own control, this operating status
can differ from the operating status of the cooling distribution circuit controller.
Signal value:
Cooling distribution circuit: Pump B relay status
The module has this BACnet output object if the Yes option is selected for the
Outputs the status of the second pump from the cooling distribution circuit controller.
Signal value:
Cooling distribution circuit: Pump B fault
The module has this BACnet output object if the Yes option is selected for the
selected for the
Outputs the fault status provided by the second pump.
Signal value:
366 2CDC508198D0211 Rev. A | AC/S 1.x.1
Override by WebUI
parameter.
0 = Off
1 = On
Pump display operating status
parameter.
0 = Inactive
1 = Active
0 = Off
1 = On
Pump display pump fault status
0 = Inactive
1 = Active
Double pump
Double pump
Double pump
Double pump
parameter.
Object type
Unit
Binary value
-
parameter and the Yes option is
Binary value
-
parameter and the Yes option is
Binary value
-
parameter.
Binary value
-
parameter and the Yes option is
COV send
condition
-
-
-
-