Connection To The Internet; Open Ip Network Ports - ABB i-bus KNX AC/S 1.x.1 Series Product Manual

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Safety
2.7

Connection to the Internet

KNXnet/IP routing and KNXnet/IP tunneling use unencrypted data transfer and is therefore not intended
for use on the public internet. For this reason router ports in the direction of the internet must not be
opened: this action will ensure KNX communication is not visible on the internet.
Systems can be accessed via the internet in the following ways:
Access to KNX installations via VPN connections. However, this requires a router with VPN server
functionality or a server.
Use of manufacturer-specific solutions or visualizations, e.g. access via https.
2.8

Open IP network ports

The device uses the following network ports for data communication in the IP network. It is to be ensured
that only authorized systems have access to these network ports.
Port
27360 TCP
1900 TCP
80, 443 TCP
123 UDP
47808 UDP
3671 TCP+UDP
2403 TCP
Table 2: Open IP network ports
Limitation
Protocol
20/minute
SSH
15/second
i-bus
15/second
http, https
20/second
NTP
30/second
BACnet
30/second
KNX
30/second
Automation ASM
Remark
Only if SSH access has been
activated
®
Tool
WebUI
Only if NTP is activated
Only if BACnet is activated.
The port can be changed.
For the KNX download
Monitor mode.
Only if access has been activated.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 13