ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 207

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object function
Input: On/Off confirm (slave)
The module has this group object if the Display+set (slave) option is selected for the
This group object is used for synchronization between the Room ASM (slave) and the room thermostat (master). For this
purpose the group object must be connected to the controller's (master's) group object of the same name.
In this group object the room thermostat (master) confirms to the Room ASM (slave) whether it is currently switched on or off
Telegram value:
Output: On/Off request (slave)
The module has this group object if the Display+set (slave) option is selected for the
This group object is used for synchronization between the Room ASM (slave) and the room thermostat (master). For this
purpose the group object must be connected to the controller's (master's) group object of the same name.
The Room ASM sends the switch on or switch off request to the controller in this group object.
Telegram value:
Input: Heating/cooling operating type
The module has this group object if the Display option is selected for the
Input for the connection of the heating/cooling operating type from the room thermostat.
Telegram value:
Name (can be changed
separately)
Room
0 = Off
1 = On
Room
0 = Off
1 = On
Room
0 = Cooling
1 = Heating
Data type
1 bit
DPT 1.001
Controller On/Off
parameter.
1 bit
DPT 1.001
Controller On/Off
parameter.
1 bit
DPT 1.100
Heating/cooling operating type
parameter.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 207
Flags
C, W, T, U
C, T
C, W, T, U